- Range of Product
- Altivar 61
- Product or Component Type
- Variable speed drive
- Product Specific Application
- Pumping and ventilation machine
- Component name
- ATV61
- Motor power kW
- 30 kW, 3 phase 380...480 V
- Maximum Horse Power Rating
- 40 hp, 3 phase 380...480 V
- power supply voltage
- 380...480 V - 15...10 %
- supply number of phases
- 3 phase
- Line current
- 56 A 480 V 3 phase 30 kW / 40 hp 66 A 380 V 3 phase 30 kW / 40 hp
- EMC filter
- Level 3 EMC filter
- Variant
- Reinforced version
- Assembly style
- With heat sink
- Apparent power
- 43.4 kVA 380 V 3 phase 30 kW / 40 hp
- maximum prospective line Isc
- 22 kA 3 phase
- Maximum transient current
- 79.2 A 60 s, 3 phase
- Nominal switching frequency
- 12 kHz
- Switching frequency
- 1...16 kHz adjustable 12...16 kHz with derating factor
- asynchronous motor control
- Voltage/frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, 2 points Voltage/frequency ratio, 5 points Flux vector control without sensor, standard
- Synchronous motor control profile
- Vector control without sensor, standard
- Communication Port Protocol
- CANopen Modbus
- Type of polarization
- No impedance Modbus
- Option card
- Communication card APOGEE FLN Communication card BACnet Communication card CC-Link Controller inside programmable card Communication card DeviceNet Communication card EtherNet/IP Communication card Fipio I/O extension card Communication card Interbus-S Communication card LonWorks Communication card...
- Product destination
- Asynchronous motors Synchronous motors
- power supply voltage limits
- 323…528 V
- power supply frequency
- 50...60 Hz - 5...5 %
- power supply frequency limits
- 47.5...63 Hz
- Continuous output current
- 52 A 12 kHz, 460 V - 3 phase 66 A 12 kHz, 380 V - 3 phase
- Output frequency
- 0.1…599 Hz
- Speed range
- 1…100 in open-loop mode, without speed feedback
- Speed accuracy
- +/- 10 % of nominal slip 0.2 Tn to Tn without speed feedback
- Torque accuracy
- +/- 15 % in open-loop mode, without speed feedback
- Transient overtorque
- 130 % of nominal motor torque +/- 10 % 60 s
- Braking torque
- 30 % without braking resistor
- Regulation loop
- Frequency PI regulator
- Motor slip compensation
- Not available in voltage/frequency ratio (2 or 5 points) Adjustable Can be suppressed Automatic whatever the load
- diagnostic
- 1 LED (red) for drive voltage
- Output voltage
- <= power supply voltage
- electrical isolation
- Between power and control terminals
- type of cable for mounting in an enclosure
- With an IP21 or an IP31 kit 3 IEC cable 104 °F (40 °C), copper 70 °C / PVC With UL Type 1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR
- Electrical connection
- Terminal 2.5 mm² / 14 AWG AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR) Terminal 50 mm² / 1/0 AWG L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB)