- Range of product
- Altivar 61
- Product or component type
- Variable speed drive
- Product specific application
- Pumping and ventilation machine
- Component name
- ATV61
- Motor power kW
- 0.75 kW, 3 phases at 380...480 V
- Motor power hp
- 1 hp, 3 phases at 380...480 V
- power supply voltage
- 380...480 V - 15...10 %
- supply number of phases
- 3 phases
- Line current
- 1.5 A for 480 V 3 phases 0.75 kW / 1 hp 1.8 A for 380 V 3 phases 0.75 kW / 1 hp
- EMC filter
- Class C1 EMC filter integrated
- Assembly style
- Enclosed
- Apparent power
- 1.2 kVA at 380 V 3 phases 0.75 kW / 1 hp
- maximum prospective line Isc
- 5 kA for 3 phases
- Maximum transient current
- 2.5 A for 60 s, 3 phases
- Nominal switching frequency
- 8 kHz
- Switching frequency
- 2...16 kHz adjustable 8...16 kHz with derating factor
- asynchronous motor control
- Voltage/frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, 2 points Voltage/frequency ratio, 5 points Flux vector control without sensor, standard
- Synchronous motor control profile
- Vector control without sensor, standard
- Communication port protocol
- Modbus CANopen
- Type of polarization
- No impedance for Modbus
- Option card
- Communication card for APOGEE FLN Communication card for BACnet Communication card for CC-Link Controller inside programmable card Communication card for DeviceNet Communication card for EtherNet/IP Communication card for Fipio I/O extension card Communication card for Interbus-S Communication card...
- Product destination
- Asynchronous motors Synchronous motors
- power supply voltage limits
- 323…528 V
- power supply frequency
- 50...60 Hz - 5...5 %
- power supply frequency limits
- 47.5...63 Hz
- Continuous output current
- 2.1 A at 8 kHz, 460 V - 3 phases 2.3 A at 8 kHz, 380 V - 3 phases
- Output frequency
- 0.1…599 Hz
- Speed range
- 1…100 in open-loop mode, without speed feedback
- Speed accuracy
- +/- 10 % of nominal slip 0.2 Tn to Tn without speed feedback
- Torque accuracy
- +/- 15 % in open-loop mode, without speed feedback
- Transient overtorque
- 130 % of nominal motor torque +/- 10 % for 60 s
- Braking torque
- 30 % without braking resistor
- Regulation loop
- Frequency PI regulator
- Motor slip compensation
- Automatic whatever the load Can be suppressed Adjustable Not available in voltage/frequency ratio (2 or 5 points)
- diagnostic
- 1 LED (red) for drive voltage
- Output voltage
- <= power supply voltage
- electrical isolation
- Between power and control terminals
- type of cable for mounting in an enclosure
- With an IP21 or an IP31 kit: 3 wire(s)IEC cable at 40 °C, copper 70 °C / PVC With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
- Electrical connection
- Terminal 2.5 mm² / 14 AWG (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR) Terminal 6 mm² / 8 AWG (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB)
- Tightening torque
- 0.6 N.m (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR) 1.4 N.m, 12.3 lb.in (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB)