- Ürün kodu
- SR2E121FU
- Marka
- Schneider Electric
- Ürün grubu
- Schneider Electric › PLC ve Kontrol Sistemleri › Zelio Logic › Akıllı Röle / Aksesuar
- Durum
- Yeni
- Stok durumu
- Sorunuz
- Range of Product
- Zelio Logic
- Product or Component Type
- Compact smart relay
- Local display
- Without
- Number or control scheme lines
- 0…240 ladder 0…500 FBD
- Cycle time
- 6…90 ms
- Backup time
- 10 years 77 °F (25 °C)
- Clock drift
- 12 min/year 32…131 °F (0…55 °C) 6 s/month 77 °F (25 °C)
- Checks
- Program memory on each power up
- [Us] rated supply voltage
- 100...240 V AC
- Supply voltage limits
- 85…264 V
- Supply frequency
- 50/60 Hz
- Maximum supply current
- 30 mA 240 V without extension) 80 mA 100 V without extension)
- Power consumption in VA
- 7 VA without extension
- Isolation voltage
- 1780 V
- Protection Type
- Against inversion of terminals (control instructions not executed)
- Discrete input number
- 8
- Discrete input voltage
- 100...240 V AC
- Discrete input current
- 0.6 mA
- Discrete input frequency
- 57...63 Hz 47...53 Hz
- Voltage state 1 guaranteed
- >= 79 V discrete input
- Voltage state 0 guaranteed
- <= 40 V discrete input
- Current state 1 guaranteed
- >= 0.17 mA discrete input)
- Current state 0 guaranteed
- <= 0.5 mA discrete input)
- Analogue input number
- 0
- Input impedance
- 350 kOhm discrete input
- Number of Outputs
- 4 relay
- Output voltage limits
- 5...30 V DC relay output) 24...250 V AC
- Contacts type and composition
- NO relay output
- Output thermal current
- 8 A for all 4 outputs relay output
- Electrical durability
- AC-12 500000 cycles 230 V, 1.5 A relay output IEC 60947-5-1 AC-15 500000 cycles 230 V, 0.9 A relay output IEC 60947-5-1 DC-12 500000 cycles 24 V, 1.5 A relay output IEC 60947-5-1 DC-13 500000 cycles 24 V, 0.6 A relay output IEC 60947-5-1
- Switching capacity in mA
- >= 10 mA 12 V relay output)
- Operating rate in Hz
- 0.1 Hz at Ie)relay output 10 Hz no load)relay output
- Mechanical durability
- 10000000 cycles relay output
- [Uimp] rated impulse withstand voltage
- 4 kV EN/IEC 60947-1 and EN/IEC 60664-1
- Clock
- With
- Response time
- 50 ms ladder from state 0 to state 1)discrete input 50 ms ladder from state 1 to state 0)discrete input 50...255 ms FBD from state 0 to state 1)discrete input 50...255 ms FBD from state 1 to state 0)discrete input 10 ms from state 0 to state 1)relay output 5 ms from state 1 to state 0)relay output
- Connections - terminals
- Screw terminals, 1 x 0.2...1 x 2.5 mm² 25 AWG...14 AWG) semi-solid Screw terminals, 1 x 0.2...1 x 2.5 mm² 25 AWG...14 AWG) solid Screw terminals, 1 x 0.25...1 x 2.5 mm² 24 AWG...14 AWG) flexible with cable end Screw terminals, 2 x 0.2...2 x 1.5 mm² 24 AWG...16 AWG) solid Screw terminals, 2 x 0.25......
- Tightening torque
- 4.4 lbf.in (0.5 N.m)
- Overvoltage category
- III conforming to IEC 60664-1
- Net Weight
- 0.49 lb(US) (0.22 kg)