- Range of Product
- Modicon TM3 Safety
- Product or Component Type
- Safety module
- Device short name
- TM3SAC
- Safety module application
- For emergency stop and switch monitoring
- Function of module
- Emergency stop monitoring 1-channel wiring Emergency stop monitoring 2-channel wiring Monitoring of a movable guard with 2 switches and automatic start
- Safety level
- Can reach PL d/category 3 ISO 13849-1 2008 Can reach PL d/category 3 ISO 13849-2 2012 Can reach SILCL 2 IEC 62061 2005 Can reach SIL 2 IEC 61508 2010
- Safety reliability data
- DC = 95 % ISO 13849-1 SFF = 95 % IEC 61508-1 HFT = 1 IEC 61508-1 Type = A IEC 61508-1 PFHd = 5E-9 1/h IEC 61508-1 PFHd = 30E-9 1/h IEC 61508-1 MTTFd = 500 years ISO 13849-1 MTTFd = 85 years ISO 13849-1
- Synchronisation time between inputs
- Unlimited
- Connections - terminals
- Captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34 Captive spring terminals, removable terminal block 1 x 0.25...1...
- Output type
- Relay instantaneous opening, 3 NO, potential free
- Number of safety circuits
- 3 NO relay instantaneous opening
- Maximum switching voltage
- 230 V AC-15 50 Hz relay instantaneous opening) 24 V DC-13 relay instantaneous opening)
- [Us] rated supply voltage
- 24 V - 15...20 % DC
- Power consumption in W
- 0.2 W 5 V DC 3.6 W 24 V DC
- Input protection type
- Internal, electronic
- [Uc] control circuit voltage
- 24 V DC
- Maximum cable distance between devices
- 98.4 ft (30 m)
- Breaking capacity
- 360 VA holding AC-15 B300 relay output 3600 VA inrush AC-15 B300 relay output
- Output thermal current
- 6 A per relay relay output
- [Ith] conventional free air thermal current
- 18 A
- Associated fuse rating
- 4 A gG or gL relay output IEC 60947-5-1 6 A fast blow relay output IEC 60947-5-1
- Minimum output current
- 10 mA relay output
- Output voltage
- 10 V relay output
- Maximum response time on input open
- 40 ms
- [Ui] rated insulation voltage
- 300 V 2)IEC 60647-5-1
- [Uimp] rated impulse withstand voltage
- 4 kV III IEC 60647-5-1
- Current consumption
- 100 mA 24 V DC external supply
- Local signalling
- 6 LEDs (green/red) for user
- Electrical Connection
- Spring terminal
- Standards
- ISO 13849-1:2008 ISO 13849-2:2012 IEC 62061:2005 IEC 61508:2010 IEC 60947-5-1:2010 IEC 61131-2:2007 IEC 60204-1:2005 IEC 60204-1:2009/A1 IEC 61010-1:2010 EN 50581:2012
- Product Certifications
- UL 61010-2-201 CSA 61010-2-201 (pending) TÜV EAC CSA Haz Loc Class 1 Division 2 (pending) ANSI Haz Loc Class 1 Division 2 (pending) RCM
- Marking
- CSA EAC CE RCM UL TÜV EFUP 10
- Electromagnetic compatibility
- Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2 Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2 Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz to 1 GHz) conforming to...
- Mounting support
- Top hat type TH35-7.5 rail IEC 60715 Top hat type TH35-15 rail IEC 60715 wall mount using attached fasteners
- Height
- 3.7 in (94 mm)
- Depth
- 2.9 in (73 mm)
- Width
- 1.7 in (43.7 mm)
- Net Weight
- 0.42 lb(US) (0.19 kg)
- Resistance to electrostatic discharge
- 8 kV in air IEC 61000-4-2 6 kV on contact IEC 61000-4-2
- Resistance to electromagnetic fields
- 9.1 V/m (10 V/m) 80 MHz...1 GHz IEC 61000-4-3 2.7 V/m (3 V/m) 1.4 GHz...2 GHz IEC 61000-4-3 0.9 V/m (1 V/m) 2 GHz...3 GHz IEC 61000-4-3