- Range of Product
- Modicon TM3
- Product or Component Type
- Parallel interface module
- Product Specific Application
- TeSys U
- [Us] rated supply voltage
- 24 V DC external supply - 15...20 %)
- Number of input channels
- 12
- Number of output channels
- 8
- Range Compatibility
- Modicon M221 Modicon M251 Modicon M241 Modicon M262
- Current consumption
- 5 mA 5 V DC via bus connector at state on 35 mA 5 V DC via bus connector at state off 0 mA 24 V DC via bus connector at state on 10 mA 24 V DC via bus connector at state off 1200 mA 24 V DC external power supply at state on
- Input voltage limits
- 19.2...28.8 V per input
- Input current limits
- 5 mA per input
- Response time
- < 10 ms turn-off input
- Output voltage
- 24 V DC transistor output
- Maximum load current
- 800 mA per channel starting mode 100 ms 300 mA per channel normal mode
- Insulation
- Between the RJ45 connectors and internal logic 500 V AC Non-insulated between RJ45 connectors
- Output protection type
- Against overload, protection technology: current limiter
- Reset
- Automatic reset
- Local signalling
- 3 LEDs green per channel input status 2 LEDs green per channel output status
- Electrical connection
- 3 x 2.5 mm² removable screw terminal block with pitch 5.08 mm adjustment for connecting the 24 V DC power supply 4 RJ45 connectors for connecting the motor starters
- Mounting support
- Top hat type TH35-15 rail IEC 60715 Top hat type TH35-7.5 rail IEC 60715 plate or panel with fixing kit
- Height
- 3.5 in (90 mm)
- Depth
- 3.3 in (85 mm)
- Width
- 1.2 in (30 mm)
- Net Weight
- 0.254 lb(US) (0.115 kg)
- DC supply voltage
- 24 V
- Product Certifications
- CE cULus UKCA RCM EAC
- Marking
- CE
- Resistance to electrostatic discharge
- 8 kV in air EN/IEC 61000-4-2 4 kV on contact EN/IEC 61000-4-2
- Resistance to electromagnetic fields
- 9.1 V/m (10 V/m) 80 MHz...1 GHz EN/IEC 61000-4-3 2.7 V/m (3 V/m) 1.4 GHz...2 GHz EN/IEC 61000-4-3 0.9 V/m (1 V/m) 2 GHz...3 GHz EN/IEC 61000-4-3
- Resistance to magnetic fields
- 98.4 A/m (30 A/m) 50/60 Hz EN/IEC 61000-4-8
- Resistance to fast transients
- 1 kV inputEN/IEC 61000-4-4 1 kV outputEN/IEC 61000-4-4
- Surge withstand
- 1 kV input common mode EN/IEC 61000-4-5 1 kV output common mode EN/IEC 61000-4-5
- Resistance to conducted disturbances
- 10 V 0.15...80 MHz EN/IEC 61000-4-6 3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL)
- Electromagnetic emission
- Radiated emissions 40 dBμV/m QP class A 10 m)30…230 MHz EN/IEC 55011 Radiated emissions 47 dBμV/m QP class A 10 m)230…1000 MHz EN/IEC 55011
- Ambient Air Temperature for Operation
- 14…95 °F (-10…35 °C) vertical installation 14…131 °F (-10…55 °C) horizontal installation
- Ambient Air Temperature for Storage
- -13…158 °F (-25…70 °C)
- Relative humidity
- 10…95 %, without condensation in operation) 10…95 %, without condensation in storage)
- IP degree of protection
- IP20 with protective cover in place
- Pollution degree
- 2
- Operating altitude
- 0...6561.68 ft (0...2000 m)
- Storage altitude
- 0…9842.5 ft (0…3000 m)